Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T05ME00829
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/10/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* BLOCK & CLAMP GAS PIPE AS NOTED ON PREVIOUS INSPECTION. CONDENSATE CANNOT DRIP OVER THE EDGE OF THE ROOF. MUST TERMINATE WITHIN 6" OF DIRT OR AN AREA THAT CAN ABSORB THE WATER. BLOCK & CLAMP PVC EVERY 4' PAINT PVC W/LATEX PAINT. USE A ROOF JACK IF PENETRATING THE ROOF WITH DRAIN LINE. CHECKED GAS PIPING WITH SOAPY SOLUTION. TEST IS OK |
|
| 11/16/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*PROVIDE A CONDENSATE DRAIN TO AN APPROVED LOCATION. PROVIDE A MIN 10 LB PRESSURE TEST ON ALL NEW GAS PIPING. BLOCK & CLAMP GAS PIPE NEAR SHUT OFF VALVE TO FURNACE. LOW VOLTAGE WIRE MUST BE PROTECTED USE CONDUIT. PROVIDE A COVER ON JUNCTION BOX. BLOCK & CLAMP ELEC. CONDUIT. |