Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/04/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 11/01/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*PROVIDE A BUSHING WHERE ELECT WIRES PASS THRU THE CABINET ON A/C UNIT. CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. TERMINATE WITHIN 6" OF THE GROUND WITH AN ELBOW AND DIVERT THE WATER AWAY FROM THE HOUSE. BLOCK & CLAMP PVC EVERY 4'. IDENTIFY THE CIRCUIT BREAKER. RECALL FOR INSPECTION. |