Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/25/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE |
|
| 11/25/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*ADDITION OF SUPPLY /DUCTWORK ON ROOF RETURN HAS BLOCKED WATER HEATER VENT CAP ON ROOF TOP. NEED TO EXTEND WATER HEATER VENT PIPE ABOVE TOP OF DUCTWORK. # 2 PROVIDE FLASHING AT ROOF WHERE CONDENSATE PIPING TURNS DOWN TO GROUND AT PENETRATION. |