Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/22/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*ALL CORRECTIONS HAVE BEEN MADE | |
| 10/11/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* CAP OFF UNUSED OPENING FROM THE OLD FURNACE VENT WITH METAL, NOT FOIL TAPE CONDENSATE CANNOT DRIP OVER THE EDGE OF THIS ROOF. MUST TERMINATE TO WITHIN 6'' OF THE GROUND. SECURE THE ELEC. DISCONNECT. I.D. CIRCUIT BREAKER PROVIDE A MIN. 10 LBS PRESSURE TEST ON ALL NEW GAS PIPING. EXPOSED DUCT ON ROOF REQUIRES MIN.R8 INSULATION AS PER I.E.C.C. 1" DUCT LINER IS R4-2. RECALL FOR INPECTION |