Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05ME00750
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/16/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* ALL CORRECTIONS HAVE BEEN MADE |
|
03/16/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE FRESH AIR INTAKE ON ALL AC UNITS PAINT EXPOSED PVC W/LATEX PAINT MARK UNIT DATA PLATES W/PROPER HEAT STRIP INSTALLED & FUSE ACCORDINGLY REMOVE UNNECESSARY CONDENSATE TRAPS PROVIDE SERVICE RECEPTACLES WITHIN 25' OF AC UNITS NEED TO SEE CIRCUIT BREAKERS PROVIDE APPROVED PLANS CONDENSATE CANNOT TERMINATE ONTO A HARD SURFACE |