Permit: T05ME00736

Parcel: 136124910


Addresses:

9630 E CREEK ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
10/05/2005 MECHANICAL - FINAL Approved CORRECTIONS HAVE BEEN MADE. IVRS - Inspection :*
09/29/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A TRAP ON THE CONDENSATE DRAIN LINE
2) REPAIR THE BUSHING WHERE SUCTION LINE CONNECTS TO COIL
3) CLAMP THE ROMEX CONNECTOR ONTO THE POWER CORDS ON FURNACE
4) USE ONLY MURRAY OR SIEMENS BREAKER FOR CONDENSOR
5) PROVIDE AN ELECTRIC UPGRADE PERMIT
6) RECALL FOR FINAL INSPECTION