Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/13/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*ALL CORRECTIONS HAVE BEEN MADE. PLEASE CLOSE N.O.V | |
| 10/11/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999*PROVIDE AN ELBOW AT BOTTOM OF CONDENSATE DRAIN & DIVERT THE WATER AWAY FROM THE HOUSE. GAS LINE NOT HOLDING PRESSURE TEST GAUGE NOT WORKING FACE PLATE IS BENT. COVER IS MISSING. RECALL FOR INSPECTION |
|
| 10/07/2005 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :*WORK STILL IN PROGRESS YOUR FLEX IS UNDER RATED FOR BTU'S OF DEVICE. PLEASE READ ALL NOTES & COMPLY. SECURE YOUR GAS PIPING PROPERLY. | |
| 10/03/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection :A/C UNIT IS OVERFUSED. 40 AMP IS MAX. NEED TO SEE CIRCUIT BREAKER. IF BREAKER EXCEEDS 30MPS THEN #8 WIRE WILL BE REQUIRED. NEED TO SEE WHERE GAS IS CONNECTED INSIDE HOUSE. PROVIDE A MIN 10 LBS PRESSURE TEST ON ALL NEW GAS PIPING. REMOVE THE UNION FROM THE GAS LINE ON THE ROOF. PROVIDE ROOF JACKS ON ALL ROOF PENETRATIONS. CONDENSATE MUST TERMINATE WITHIN 6" OF THE GROUND . GAS FLEX CONNECTOR CANNOT EXCEED 3' IN LENGTH. EXPOSE PVC MUST BE PAINTED WITH LATEX PAINT. BLOCKE & CLAMPS PVC EVERY 4'. RECALL FOR INSPECTION |