Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05ME00681
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/30/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*PLEASE CLOSE N.O.V | |
09/20/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. TERMINATE TO WITHIN 6" OF THE GROUND IN AN AREA THAT CAN ABSORB THE WATER 2) REMOVE THE EXTERNAL DRAIN TRAPS AS PER MANUFACTURERS SPECS 3) SEAL ALL JOINTS ON EXPOSED DUCT WORK 4) PROVIDE ACCESS TO THE BLDG IN REAR ROOF TOP |