Permit: T05ME00681

Parcel: 122120340

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05ME00681

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/30/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*PLEASE CLOSE N.O.V
09/20/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. TERMINATE TO WITHIN 6" OF THE GROUND IN AN AREA THAT CAN ABSORB THE WATER
2) REMOVE THE EXTERNAL DRAIN TRAPS AS PER MANUFACTURERS SPECS
3) SEAL ALL JOINTS ON EXPOSED DUCT WORK
4) PROVIDE ACCESS TO THE BLDG IN REAR ROOF TOP