Inspection History Details
Inspection Status: Partial Approval
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/14/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :*SEAL TITE STILL NOT CONNECTED PROPERLY. WATER CAN LEAK INTO THE CONDUIT INSULATION IS STILL COMING APART AT THE SEAM USE CONTACT CEMENT IF NECESSARY. RECALL FOR INSPECTION |
|
| 09/08/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROPERLY SECURE ELECTRIC CONDUIT TO WALL AT CONDENSOR 2) YOU ARE REQUIRED TO HAVE A CLAMP WITHIN 3' OF EACH CONNECTION 3) CONDUIT MUST BE STRAPPED TIGHT TO THE WALL REPAIR SEAL TITE 4) PROVIDE ADEQUATE SUPPORT ON VERTICAL SECTION OF REFER LINES AT CONDENSOR INSULATION IS COMING APART ON REFER LINES. SECURE REFER LINES ON ROOF 5) PROVIDE A HOSE CLAMP ON CONDENSATE PUMP 6) TIGHTEN THE ROMEX CONNECTOR ON THE FURNACE ONTO THE POWER CORD 7) EXTEND FURNACE VENT 2' ABOVE EVAP COOLER |