Permit: T05ME00665

Parcel: 136081220


Addresses:

9501 E 30TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Date Description Inspector Results Comments
10/26/2005 MECHANICAL - INTERMEDIATE Approved 1) 14 PSI TEST IS OK
2) CORRECTIONS HAVE BEEN MADE
09/07/2005 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) CIRCUIT BREAKER FOR A/C UNIT MUST BE SIEMENS. YOU CANNOT USE WHITE WIRE AS A CONDUCTOR. TAPE BOTH ENDS OF WIRE WITH BLACK TAPE. SECURE THE COVER ON THE SLB ON ROOF. PAINT ALL EXPOSED PVC WITH LATEX PAINT. PROVIDE A MINIMUM 10 POUND PRESSURE TEST ON ALL NEW GAS PIPING. PRESSURE GAUGE TO BE IN 1/10 INCRUMENTS