Permit: T05ME00593

Parcel: 13617321C


Addresses:

3212 S MORMON DR


Inspection Status: Not ready for Inspection

Inspection History: MECHANICAL - FINAL

Permit Number - T05ME00593

Inspection Description - MECHANICAL - FINAL

Inspection Status - Not ready for Inspection

Date Description Inspector Results Comments
09/07/2005 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
09/06/2005 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) PROVIDE 3-GALV SCREWS AT EVERY JOINT OF FURNACE VENT PIPING. SINGLE WALL REQUIRES 6" MINIMUM CLEARANCE FROM COMBUSTIBLES
2) REMOVE KINK FROM CONDENSATE PUMP PIPING
3) FURNACE VENT PIPING TO TERMINATE 2' ABOVE TOP OF COOLER INTAKE WITHIN 10' OF INTAKE AND BE SECURED PROPERLY
4) PROVIDE CORRECT OVER CURRENT PROTECTION FOR APPLIANCES