Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/26/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS ARE OK |
|
| 08/25/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) PAINT PVC-BLOCK/CLAMP |
|
| 08/11/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) PROVIDE CORRECT OVER CURRENT PROTECTION FOR BOTH UNITS ON ROOF 2) PROVIDE P-TRAP FOR CONDENSATE DRAINS WITH TERMINATION OF DRAIN 6" FROM FINISH ELEVATION. PROVIDE MINIMUM ? ON DRAIN PIPING AND SUPPORT CORRECTLY ON ROOF 3) ELECTRICAL CONNECTION INTO BREAKER PANEL IS REQUIRED TO BE WEATHER TIGHT CONNECTION |