Permit: T05ME00521

Parcel: 119043030


Addresses:

3406 S LUNDY AV #02

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
01/13/2010 MECHANICAL - FINAL Approved
03/06/2009 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
03/05/2009 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
ITEMS 10 AND 6 DATED 2/9/09 STILL NOT COMPLETE
02/23/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE ROOF ACCESS
02/09/2009 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE R-8 INSULATION ON ALL EXTERIOR DUCT
2. RTU BRANCH TAP IS BACKWARDS AT SUPPLY
3. UNIT (RTU) NOT LEVEL
4. RTU NOT SPANNING TRUSSES AT SUPPORTS
5. SEAL TITE MUST BE SUPPORTED OFF OF ROOF
6. PVC TO BE PAINTED
7. PVC TO BE PROPERLY SECURED TO BUILDING
8. PVC TO BE SUPPORTED NOT TO EXCEED 48"
9. PROVIDE SEDIMENT TRAP AT GAS PIPING
10. PROVIDE GAS PRESSURE TEST