Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/13/2010 | MECHANICAL - FINAL | Approved | ||
| 03/06/2009 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/05/2009 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* ITEMS 10 AND 6 DATED 2/9/09 STILL NOT COMPLETE |
|
| 02/23/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE ROOF ACCESS |
|
| 02/09/2009 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE R-8 INSULATION ON ALL EXTERIOR DUCT 2. RTU BRANCH TAP IS BACKWARDS AT SUPPLY 3. UNIT (RTU) NOT LEVEL 4. RTU NOT SPANNING TRUSSES AT SUPPORTS 5. SEAL TITE MUST BE SUPPORTED OFF OF ROOF 6. PVC TO BE PAINTED 7. PVC TO BE PROPERLY SECURED TO BUILDING 8. PVC TO BE SUPPORTED NOT TO EXCEED 48" 9. PROVIDE SEDIMENT TRAP AT GAS PIPING 10. PROVIDE GAS PRESSURE TEST |