Permit: T05ME00520

Parcel: 133403630


Addresses:

7744 E ROSEWOOD ST

Inspection Status: Denied

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/25/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) INCORRECT FUSING
2) 5 KW AUX. HEAT STRIP DOES NTO FUSE AT 40 AMPS
3) RE-MARK INSIDE OF SWITCH WITH MARKER
08/09/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) 40 AMP FUSES ARE TO LARGE FOR A/C UNIT-30 AMP IS MAX
2) IS THERE A HEAT STRIP ? IDENTIFY DATA PLATE AND FUSE ACCORDINGLY
3) CONDENSATE CANNOT DRIP OVER THE EDGE OF THE ROOF. MUST TERMINATE 6" ABOVE THE GROUND