Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
Permit Number - T05ME00520
Inspection Description - MECHANICAL - FINAL
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/25/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) INCORRECT FUSING 2) 5 KW AUX. HEAT STRIP DOES NTO FUSE AT 40 AMPS 3) RE-MARK INSIDE OF SWITCH WITH MARKER |
|
08/09/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 40 AMP FUSES ARE TO LARGE FOR A/C UNIT-30 AMP IS MAX 2) IS THERE A HEAT STRIP ? IDENTIFY DATA PLATE AND FUSE ACCORDINGLY 3) CONDENSATE CANNOT DRIP OVER THE EDGE OF THE ROOF. MUST TERMINATE 6" ABOVE THE GROUND |