Permit: T05ME00497

Parcel: 133170240

Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T05ME00497

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2005 MECHANICAL - INTERMEDIATE Approved
08/02/2005 MECHANICAL - INTERMEDIATE Partial Approval 1) BLOCK/CLAMP, PAINT CONDENSATE PIPING, PVC. VERIFY IF UNIT DUMPING ON SIDEWALK OR PARKING LOT
2) NEED 40 AMP FUSE, UNIT FUSES AT 40 MAX, NO AUX. HT. STRIP. MARK DATA PLATE ON UNIT.
3) OAS. (OUTSIDE AIR INTAKE) ON RETURN AIR