Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/24/2011 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/22/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : A reinspection fee has been assessed for this inspection. Multiple inspectio |
|
| 08/10/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/14/2011 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE ACCESS TO ROOF 2. PROVIDE A ROOF JACK AT CONDENSATE PENETRATION 3. USE ONLY OUTDOOR FITTINGS ON ELEC CONDUIT 4. REDUCING WASHERS ARE TOO SMALL AT CIRCUIT PANEL 5. SECURE THE HEAT STRIP DISCONNECT 6. PROPERLY SUPPORT ELEC CONDUIT + CONDENSATE DRAIN. USE REDWOOD OR PRESSURE TREATED WOOD. 7. BE SURE ANGLE IRON STAND IS SECURED TO ROOF |