Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/14/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/27/2005 | MECHANICAL - FINAL | Denied | 1) PROVIDE A PERMIT FOR THE NEW WATER HEATER 2) PROVIDE MINIMUM 3 SCREWS IN ALL JOINTS AT VENT CONNECTORS 3) RELOCATE REFER LINES FROM BLOCKING REMOVAL OF WATER HEATER. SECURE THE STAT WIRE AND CONDENSATE DRAIN HOSE 4) T & P RELIEF DRAIN CANNOT RUN UP HILL AND HAVE NO COPPER FLEX ON DRAIN. PROVIDE METHOD OF RUNNING T & P DRAIN. BOTH FLEX COPP WATER LINES ARE KINKED AND FLATTENED. REPAIR OR REPLACE AS NEEDED 5) REINSTALL COVER PLATE MISSING ON CONDENSOR. ISOLATE COPPER DISCHARGE LINE FROM CONTACTING STEEL STRAP |
|
| 07/26/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* HOMEOWNER SAID UNIT IN REAR OF HOUSE - GATES LOCKED NO FURTHER RESPONSE AT FRONT DOOR -- ORGANIZE CALL FOR INSPECTION WHEN UNIT CAN BE ACCESSED. |