Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* GAS PRESS. TEST - OK |
|
| 04/17/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* SYSTEM 11 PSI WILL NOT MAINTAIN PRESS -- |
|
| 04/05/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GAS PIPING MUST MAINTAIN 10 PSI MIN. |
|