Permit: T05ME00422

Parcel: 128111500


Addresses:

4701 E SCARLETT ST

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
07/07/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :* THE VENT ON THE CONDENSATE DRAIN MUST BE DOWNSTREAM OF THE TRAP. INSTALL AN ELBOW ON THE END OF THE CONDENSATE DRAIN PIPE & DIVERT THE WATER AWAY FROM THE HOUSE. RECALL FOR INSPECTION.