Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/21/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 07/19/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) 60 AMP FUSES ARE TO LARGE. 35 AMP IS MAX. 2) PROVIDE A SHEET METAL CAP WHERE OLD FURNACE VENT CONNECTED TO EXISTING FLUE PIPE 3) 30 PSI TEST ON GAS PIPE IS OK |
|
| 06/27/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* GAS LINE IS NOT HOLDING PRESSURE. NEED TO SEE WHERE GAS IS CONNECTED INSIDE HOME. CAP OFF THE CLEANOUT ON THE CONDENSATE DRAIN. PROVIDE AN ELECTRICAL CIRCUIT & FUSES FOR DISCONNECT ON ROOF. |