Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date |
Description |
Inspector |
Results |
Comments |
| 07/13/2005 |
MECHANICAL - FINAL |
|
Approved |
IVRS - Inspection :* |
| 06/26/2005 |
MECHANICAL - FINAL |
|
Partial Approval |
IVRS - Inspection :* 1) CONDENSATE DRAIN. A) IMPROPER TERMINATION B) OPEN VENT FOLLOW S TRAP, NOT AHEAD OF IT. C) PVC NEEDS TO BE PAINTED. 2) ELECTRIC HI VOLTAGE CONDUIT ACCROSS ROOF. RAISE BLOCK & CLAMP. NEED TEE TOP FLASHING ON ROOF ?? VOLTAGE. 3) IMPROPER FUSE SIZE. NO AUX. HEAT STRIP MARKED ON DATA PL??. 4) MARK CIR. BLR. PANEL FOR A/C CIRCUIT. |