Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
06/16/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
06/13/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* GAS LINE NOT HOLDING PRESSURE. 60 LBS TEST GAUGE NOT ACCEPTABLE. GAUGE MUST BE IN 1 /10 TH INCREMENTS.
06/09/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) NO CORRECTIONS HAVE BEEN MADE
06/07/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999* CONDENSATE CANNOT DRIP FROM THE EDGE OF THE ROOF. MUST GO TO WITHIN 6" OF THE GROUND. PROVIDE A MIN. 10 LB PRESSURE TEST ON ALL NEW GAS PIPING