Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05ME00343
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/29/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS HAVE BEEN MADE |
|
08/22/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) T AND P RELIEF LINE IS NOT PITCHED FROM VALVE TO TERMINATION 2) LINE FROM T AND P INTO WALL IS PITCHED UP, INCORRECT. 3) MUST FLOW DOWN |
|
08/10/2005 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) T & P RELIEF DRAIN MUST RUN DOWNHILL 2) PROVIDE MINIMUM 3-SCEWS IN JOINTS OF WATER HEATER VENT CONNECTOR 3) EXTEND VENTS 3' ABOVE EVAP COOLER |
|
07/11/2005 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* 1) PLEASE PROVIDE ROOF ACCESS FOR VIEWING OF VENT THRU ROOF. 2) PROVIDE PERMIT FOR NEW WATER HEATER. 3) SECURE GAS PIPING TO FURNACE & WATER HEATER PROPERLY 4) WATER HEATER TEMPERATURES & PRESSURE RELIEF DRAIN TO BE RIGID APPROVED PIPING ( NO FLEX) AND GRAVITY DRAIN TO DAYLIGHT. |