Permit: T05ME00343

Parcel: 134120090

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Permit Number - T05ME00343

Inspection Description - MECHANICAL - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) CORRECTIONS HAVE BEEN MADE
08/22/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1) T AND P RELIEF LINE IS NOT PITCHED FROM VALVE TO TERMINATION
2) LINE FROM T AND P INTO WALL IS PITCHED UP, INCORRECT.
3) MUST FLOW DOWN
08/10/2005 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
1) T & P RELIEF DRAIN MUST RUN DOWNHILL
2) PROVIDE MINIMUM 3-SCEWS IN JOINTS OF WATER HEATER VENT CONNECTOR
3) EXTEND VENTS 3' ABOVE EVAP COOLER
07/11/2005 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :* 1) PLEASE PROVIDE ROOF ACCESS FOR VIEWING OF VENT THRU ROOF. 2) PROVIDE PERMIT FOR NEW WATER HEATER. 3) SECURE GAS PIPING TO FURNACE & WATER HEATER PROPERLY 4) WATER HEATER TEMPERATURES & PRESSURE RELIEF DRAIN TO BE RIGID APPROVED PIPING ( NO FLEX) AND GRAVITY DRAIN TO DAYLIGHT.