Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05ME00274
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/20/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
05/12/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1) CONDENSATE PIPING-IMPROPER TERMINATION. 2) HI VOLTAGE. A-MAX FUSE SIZE, AUX HT. STRIP, 30 AMPS. B-MARK PROPER FUSE BLOCK IN SWITCH. C- STABILIZE SWITCH BOX EXTERNALLY. THANK YOU FOR THE LADDER |