Permit: T05ME00259

Parcel: 134081260


Addresses:

917 S SARNOFF DR

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/06/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) ALL CORRECTIONS HAVE BEEN MADE
05/04/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PROVIDE A TRAP ON THE CONDENSATE DRAIN LINES PER INSTALL INSTRUCTIONS. CORRECT OVERFLOW SENSOR ON CONDENSATE PUMP
2) PROVIDE A ROMEX CONNECTOR ON POWER CORD CONNECTION TO POWER
3) GAS FLEX CONNECTOR CANNOT PENETRATE THE CABINET OF THE FURNACE. MUST BE HARD PIPE
4) PROVIDE PROTECTION WHERE DISCHARGE LINE IS SCRAPING ON COIL CABINET
5) PROVIDE MINIMUM 3 SCREWS ON EACH JOINT OF FURNACE VENT CONNECTOR. REMOVE THE TAPE FROM THE CONNECTION TO DBL WALL VENT. RELOCATE THE POWER CORD FROM TOUCHING THE FLUE VENT
6) BLOCK AND CLAMP REFER LINES ON ROOF. ISOLATE COPPER FROM TOUCHING GALVANIZED STRAPS. FUSES ARE TO LARGE. 45 AMP IS MAX FUSE SIZE