Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/11/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* 1) CORRECTIONS OK 2) GAS LINE PRESSURE TEST, 11 PSI OK 3) OK TO RECONNECT |
|
| 05/05/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SECURE THE ELECT DISCONNECT. GROUND WIRE NOT CONNECTED INSIDE DISCONNECT. BE SURE ALL THE STRANDS OF WIRE FROM THE CONDUCTORS ARE INSIDE THE LUGS. TAPE BOTH ENDS OF WHITE WIRE WITH BLACK TAPE. NEED TO SEE CIRCUIT BREAKER. 2) CONDENSATE CANNOT TERMINATE INTO A SEWER VENT. 3) PROVIDE A MIN 10 LB PRESSURE TEST ON ALL NEW GAS PIPING . NEED TO SEE WHERE GAS PIPE IS CONNECTED INSIDE HOUSE. 4) SEAL ALL JOINTS ON EXPOSED DUCT. SEAL THE TOP PART OF THE ROOF JACK WHERE IS CONNECTED INSIDE HOUSE. 4) SEAL ALL JOINTS ON EXPOSED DUCT. SEAL THE TOP PART OF THE ROOF JACK WHERE IT GOES UNDER THE ROOFING ON THE RETURN AIR DUCT. RECALL FOR INSPECTION. |