Permit: T05ME00228

Parcel: 135050910


Addresses:

6402 E CALLE MARTE

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
05/04/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
1) 14 PSI TEST IS OK
2) INSTALLER: PAINT THE EXPOSED PVC WITH LATEX PAINT
04/29/2005 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*1) PROVIDE A MIN. 10LB PRESSURE TEST ON ALL NEW GAS PIPING. BLOCK & CLAMP GAS PIPE ON ROOF. 2) PROVIDE A MIN 1/8" PER FT. SLOPE ON HORIZONTAL SECTION OF CONDENSATE DRAIN LINE. PROVIDE A ROOF JACK ON CONDENSATE DRAIN LINE. PROVIDE A PERMIT FOR ELECT. UPGRADES