Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/26/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* CORRECTIONS HAVE BEEN MADE. | |
| 04/22/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE A TRAP ON CONDENSATE DRAIN LINE. CONNECT OVERFLOW SENSOR ON PUMP. PROVIDE CLEARANCE WHERE INSULATION IS TOUCHING VENT PIPE. SUPPORT REFER LINES. PROVIDE A ROOF JACK ON ELEC- CONDUIT. IDENTIFY CIRCUIT BREAKER. |