Permit: T05ME00112

Parcel: 112061660


Addresses:

2625 N TUCSON BL

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/05/2005 MECHANICAL - FINAL Approved IVRS - Inspection :*
03/21/2005 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*1) REMOVE UNION FROM GAS LINE OR SUPPLY SHUT OFF VALVE AHEAD OF UNION. USE REVERSE THREAD NIPPLE BETWEEN UNION AND GAS VALVE. 2) REMOVE 35 AMP FUSES IN SWITCH AT UNIT, MAX. FUSE SIZE AT UNIT IS 30 AMP FOR # 10 WIRE. 3) CH.INSULATION ONDUCT WORK!