Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :*CORRECTION HAS BEEN MADE. | |
| 04/07/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 50 AMP BREAKER TOO LARGE FOR 3 TON CONDENSOR 35 AMP IS MAX. RECALL FOR INSPECTION |
|
| 03/30/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* PLEASE SCHEDULE AN INSPECTION WHEN SOMEONE WILL BE HOME |
|
| 03/08/2005 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* INSPECTED FURNACE. RECALL FOR INSPECTION ON CONDENSOR AFTER ELECTRICAL IS COMPLETED |