Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
Permit Number - T05ME00025
Inspection Description - MECHANICAL - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/24/2005 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 02/08/2005 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NEED TO SEE WHERE NEW GAS LINE IS CONNECTED INSIDE HOUSE. PROVIDE A MIN 10 LB PRESSUME TEST ON ALL NEW GAS PIPING. CONDENSATE CANNOT DRIP OVER THE EDGE OF THE ROOF. TERMIATE WITHIN 6" OF THE GROUND & DIVERT WATER AWAY FROM THE HOUSE. RECALL FOR INSPECTION. |