Inspection History Details
Inspection Status: Compliance
Inspection History: INSP - FULL
Case Number - T05FR01826
Inspection Description - INSP - FULL
Inspection Status - Compliance
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
12/14/2005 | INSP - FULL | Compliance | final on 12/09/05. | |
11/18/2005 | INSP - FULL | Correction Required | 2003 TFC-903 Sprinkler head in small closet next to the ice machine Storage shall be 18" from the head. 2003TFC-1006.1 Emergency lights shall be serviced to make sure they are in good working order at all timews. TFC-901.6 Fire sprinkler system shall be serviced annually with yag attached to the valves. TFC-906.1 shall have in the cooking area a class K-rated portable fire extinguisher. |