Inspection History Details
Inspection Status: Approved
Inspection History: INSP - REINSPECTION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/16/2005 | INSP - REINSPECTION | Approved | ok | |
| 12/02/2005 | INSP - REINSPECTION | Violation | Currently surge protectors (power tap) are being plugged into each other, this is violation of IFC 605.1. Power taps and surge protectors shall be plugged into approved receptacle, into a wall outlet only. This violation shall be abated upon receipt of this report. Also all extension cords shall be removed as permanent wiring. 2). Fire stopping has been removed from utility, UL Listed fire stopping shall be re applied, and proof of UL listing shall be given to building management. IFC 703.1.1. 3). Faceplate shall be repaired. IFC |