Case: T05FR01644

Parcel: 122091500


Addresses:

4102 E LINDEN ST


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T05FR01644

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
11/10/2005 VIOL - MEANS OF EGRESS Approved
10/20/2005 VIOL - MEANS OF EGRESS Violation TFC 2003 1008.1 All exits will be free of double-keyed deadbolts.
25.) Replace all double-keyed deadbolt locks with thumb latch deadbolts
10/20/2005 VIOL - MEANS OF EGRESS Violation TFC 2003 1027.2 Exit pathways need to be distinguishable and operate properly.
26.) the rear gate is the exit for the bedroom on the patio. The pathay must be cleanly marked and operation all the way to the street
10/20/2005 VIOL - MEANS OF EGRESS Violation TFC 2003 1027.3 Exit pathway must be keep clear.
27.) remove trash cans and couch from the exit pathway
10/20/2005 VIOL - MEANS OF EGRESS Violation TFC 1026.4 Emergency lighting.
31.) repair or replace both emergency lights