Case: T05FR01595

Parcel: 12402034D


Addresses:

1701 E 1ST ST

Inspection Status: Violation

Inspection History: INSP - FULL

Date Description Inspector Results Comments
10/12/2005 INSP - FULL Violation 1). Entryway, there is hole in ceiling. This must be repaired. IFC 703.1
2). Entryway, room is missing doorframe. This must be repaired. IFC 703.1
3). 3rd floor egress illumination light is out of service. This shall be repaired. IFC 1026.5
4). Heat detector system throughout building is in different forms of damage. Heat detector system shall be repaired, and tested, and form shall be submitted to TFD. IFC 901.6
5). Fire alarm system shall be tested and report shall be submitted to TFD. IFC 901.6
6) 2nd floor, Room 5 from left. Drywall shall be replaced. IFC 703.1
7). Stairwell door windows shall be replaced by rated glass. Proof of rated glass shall be shown at time of reinspection. IFC 703.1
8). Approved-locking devices shall be re-installed on door in stairwells. IFC 1008.1.8. IFC 1008.1.8.1



9). Remove obstructions from exit in courtyard. This includes ladders, gasoline, and bar. IFC 1027.3
10). In lobby, egress illumination light is out of service. This shall be repaired. IFC 1026.5
11). Basement, egress illumination light is out of service. This shall be repaired. IFC 1026.5