Case: T05FR01590

Parcel: 113100990


Addresses:

2611 N WARREN AV

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
10/11/2005 VIOL - MEANS OF EGRESS Approved TFC- 1003.3.1.8.2- A dedicated circuit shall be provided for the electronic delayed egress control of the exterior gate leading out of dining room.

TFC- 1027.3 Remove obstructions from exterior egress doors leading out of activities room.

TFC- 1003.3.1.8.3.- The delayed egress time frame shall not exceed 15 seconds of delay (all exterior gates).