Case: T05FR01502

Parcel: 11711096D


Addresses:

100 N STONE AV


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T05FR01502

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
12/02/2005 INSP - FULL Approved all ok
09/26/2005 INSP - FULL Violation 1). Fire drill is required. Date to be determined by 10-28-05. IFC 405.
2). Fire alarm test and inspection report shall be submitted, and all repairs shall be completed. IFC 901.6
3). Fire sprinkler inspection report shall be submitted, and all repairs shall be completed. IFC 901.6
4). Fire pump shall be tested. IFC 901.6
5). Suites 1105, 801: Remove storage from shelves with 2 feet from ceiling. IFC 315.2.1
6). Leopard Lounge basement- Repair ceiling tiles. Currently many tiles are missing. IFC 703.1