Case: T05FR01478

Parcel: 12401002B


Addresses:

1339 E 1ST ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
10/18/2005 INSP - FULL Approved
09/21/2005 INSP - FULL Violation 1). Currently there are several portable fire extinguishers on kitchen floor. These shall be mounted in an approved manner or removed. IFC 906.7 which states:

906.7 Hangers and brackets. Hand-held portable fire extinguishers, not housed in cabinets, shall be installed on the hangers or brackets supplied. Hangers or brackets shall be securely anchored to the mounting surface in accordance with the manufacturer's installation instructions.

2). Fire alarm test and inspection report required and ll required corrections shall be completed. IFC 901.6
3). Fire sprinkler test and inspection report shall be submitted, and all corrections shall be completed. IFC 901.6
4). 6-month service on kitchen hood system shall be completed. 904.11.6.4.
5). Remove wood, poster curtains, trash can from rated stairwell. IFC 1027.2
6). 2nd floor hallway. Currently there items that are obstructing exiting. Boxes, from Rm. 9, and box in front of room 16. Remove all obstructions. IFC 1027.2
7). Exit sign is being covered in sleeping porch. NEVER cover these exit signs. 1027.2
8). Mount extinguisher in mechanical room. 906.1