Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/26/2005 | INSP - FULL | Approved | approved | |
| 09/13/2005 | INSP - FULL | Violation | 1). Pull station out of wall in first floor rear exit. Shall be replaced. IFC 901.6. 2). Ceiling tiles are missing from 2nd floor hallway. Grid and tiles shall be repaired. IFC 703.1 3). 2-Egress illumination lights are missing from 2nd floor, downstairs and lobby. These shall be replace or repaired. IFC 1026.5 4). Remove all combustible material from stair well. IFC 1027.3 5). Remove storage from roof. 304.2 6). Remove candles from basement. IFC 1027.5 |