Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/18/2005 | INSP - FULL | Approved | all ok | |
| 09/02/2005 | INSP - FULL | Violation | 1). Electrical cord is running through ceiling, and is subject to mech. Damage. Shall be removed. TFC 605.1 2). All ceiling openings on 2nd floor shall have 1 hour fire resistive rating in place. TFC 703.1 3). 6- month service due on hood system TFC 904.11.6.3 4). Mount fire extinguisher in kitchen and have service performed. TFC 904.11.5 5). All smoke detectors shall be tested and repaired in needed, and smoke detector log shall be submitted to TFD. TFC 901.5 |