Inspection Status: Violation
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 08/29/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
TFC 605.1- Identified electrical hazards shall be abated. Surge protector shall be replaced. (NE side, center office) |
| 08/29/2005 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
TFC 605.3- A working space of not less than 30" width, 36" depth and 78" height shall be provided in front of electrical service equipment. |