Case: T05FR01295

Parcel: 13701007U


Addresses:

5580 S NOGALES HY

Inspection Status: Correction Required

Inspection History: INSP - FULL

Date Description Inspector Results Comments
08/18/2005 INSP - FULL Correction Required This is a comlpaint on T05FR01254
TFC-Table 1015.1 Exit access travel distance: S1 warehouse/ sprinklered building 250 feet.TFC-315.2 storage in building: Storage of combustible material 18 incches below sprinker head. TFC-1008.1.8 Door operations: shall exit without the use of a key and special knowledge.