Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T05FR01257
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/19/2005 | INSP - FULL | Approved | partial OK | |
| 08/11/2005 | INSP - FULL | Violation | 3404.2.13.2.1 Temporarily out of service. Above-ground tanks temporarily out of service shall have all connecting lines isolated from the tank and be secured against tampering. Exception: In-place fire protection (foam) system lines. 3404.2.13.2.2 Out of service for 90 days. Above-ground tanks not used for a period of 90 days shall be safeguarded in accordance with Section 3404.2.13.1.2 or removed in accordance with Section 3404.2.14. Exceptions: 1. Tanks and containers connected to oil burners that are not in use during the warm season of the year or are used as a backup heating system to gas. 2. In-place, active fire protection (foam) system lines. 3404.2.13.2.3 Out of service for 1 year. Above-ground tanks that have been out of service for a period of 1 year shall be removed in accordance with Section 3404.2.14. Exception: Tanks within operating facilities. Please complete the following: 1). Please isolate all connecting lines from tanks, and maintain security from tampering by September 19, 2005 2). Please remove tanks within one year. A picture of tanks is enclosed for your reference. |