Case: T05FR01257

Parcel: 107070170


Addresses:

1102 W GRANT RD

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
09/19/2005 INSP - FULL Approved partial OK
08/11/2005 INSP - FULL Violation 3404.2.13.2.1 Temporarily out of service.
Above-ground tanks temporarily out of service shall have all connecting lines isolated from the tank and be secured against tampering.
Exception: In-place fire protection (foam) system
lines.

3404.2.13.2.2 Out of service for 90 days.
Above-ground tanks not used for a period of 90 days shall be safeguarded in accordance with Section 3404.2.13.1.2 or removed in accordance with Section 3404.2.14.
Exceptions:
1. Tanks and containers connected to oil burners that are not in use during the warm season of the year or are used as a backup
heating system to gas.
2. In-place, active fire protection (foam) system
lines.

3404.2.13.2.3 Out of service for 1 year.
Above-ground tanks that have been out of service for
a period of 1 year shall be removed in accordance with
Section 3404.2.14.
Exception: Tanks within operating facilities.







Please complete the following:

1). Please isolate all connecting lines from tanks, and maintain security from tampering by September 19, 2005
2). Please remove tanks within one year.
A picture of tanks is enclosed for your reference.