Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T05FR01250
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2005 | INSP - FULL | Approved | ||
08/11/2005 | INSP - FULL | Correction Required | TFC- 1008.1.8 front door key lock shall have the sign that reads: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED. TFC- 605.3 Upper floor in the electrical room, wires exposed need to repair J-box. TFC- 703.1 Tiles missing in the electrical room, need to maintain fire resistive construction inn this room TFC-703.1 also in the computer room. TFC-906. Storage shall be 18 inches below the ceiling in the pharmacy area, sprinklered building. TFC-605.9.1 Multi plug adapter shall be replaced with POWER SURGE PROTECTORS in all registers up front. |