Case: T05FR01250

Parcel: 13623007Y

Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T05FR01250

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
08/30/2005 INSP - FULL Approved
08/11/2005 INSP - FULL Correction Required TFC- 1008.1.8 front door key lock shall have the sign that reads: THIS DOOR TO REMAIN UNLOCKED WHEN BUILDING IS OCCUPIED.
TFC- 605.3 Upper floor in the electrical room, wires exposed need to repair J-box.
TFC- 703.1 Tiles missing in the electrical room, need to maintain fire resistive construction inn this room TFC-703.1 also in the computer room.
TFC-906. Storage shall be 18 inches below the ceiling in the pharmacy area, sprinklered building.
TFC-605.9.1 Multi plug adapter shall be replaced with POWER SURGE PROTECTORS in all registers up front.