Case: T05FR01231

Parcel: 12404050A


Addresses:

1535 E 1ST ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
09/01/2005 INSP - FULL Approved all approved
08/08/2005 INSP - FULL Violation 1). Currently tag or certificate indicating hood system maintenance is missing. Apply tag or certificate to hood extinguishing system appliance. IFC 904.11.6.4

2). Egress illumination light in basement is out of service. Shall be repaired. IFC 1025.5

3). Remove top layer of boxes from basement storage. No storage may be within 2 feet from ceiling. IFC 315.2.1