Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/01/2005 | INSP - FULL | Approved | all approved | |
| 08/08/2005 | INSP - FULL | Violation | 1). Currently tag or certificate indicating hood system maintenance is missing. Apply tag or certificate to hood extinguishing system appliance. IFC 904.11.6.4 2). Egress illumination light in basement is out of service. Shall be repaired. IFC 1025.5 3). Remove top layer of boxes from basement storage. No storage may be within 2 feet from ceiling. IFC 315.2.1 |