Case: T05FR01229

Parcel: 13502134B


Addresses:

6980 E 22ND ST


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T05FR01229

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
08/19/2005 INSP - FULL Approved
08/05/2005 INSP - FULL Correction Required TFC-1003.6 The front door exit is blocked with sales display. shall maintain 48 inchs to the exit.
TFC-102.6 Need to post thr Certificate of Occupancy.
TFC-1003.6 South west exit door blocked with boxes need a 36 inch exit way for employees only area.
TFC- 906.1 Fire extinguisher missing next to the south/west exit.
TFC-906.6 Sprinkler system spare sprinkler box needs to be repaired,also need more sprinkler heads in storage box.
TFC-703.1 Tile missing in the stock room, this is to maintain fire resistive contruction above sprinklers.
TFC-1006.1 Test the emergency back up lights,at least every three months.
TFC-Fire extinguisher in stock room needs to be mounted.