Case: T05FR01190

Parcel: 13216596A


Addresses:

1320 E BENSON HY


Inspection Status: Compliance

Inspection History: VIOL - WELDING & OTHER HOT WRK

Case Number - T05FR01190

Inspection Description - VIOL - WELDING & OTHER HOT WRK

Inspection Status - Compliance

Date Description Inspector Results Comments
10/10/2005 VIOL - WELDING & OTHER HOT WRK Compliance operation removed
08/01/2005 VIOL - WELDING & OTHER HOT WRK Violation 2604.1.1 - hot work areas shall not contain combustibles - welding table made of wood
08/01/2005 VIOL - WELDING & OTHER HOT WRK Violation 2604.2.6 - a minimum of one extinguisher with a minimum rating 2A:20B:C shall be readily accessible within 30'
08/01/2005 VIOL - WELDING & OTHER HOT WRK Violation 2606.4 - a switch or circuit breaker shall be marked EMERGENCY DISCONNECT and shall be visible from the welding equipment
08/01/2005 VIOL - WELDING & OTHER HOT WRK Violation 2606.5 - damaged cables shall be removed from service until properly repaired or replaced - arc welder and wire feed welder leads