Inspection Status: Compliance
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
Case Number - T05FR01190
Inspection Description - VIOL - BUILDING SVCS & SYSTEMS
Inspection Status - Compliance
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/10/2005 | VIOL - BUILDING SVCS & SYSTEMS | Compliance | ||
| 08/01/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.3 - a working space of not less than 30''w x 36''d x 78''h shall be provided in front of electrical service equipment - main panel at pole outside, sub panel in shop | |
| 08/01/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.4 - multiplug adapters shall be prohibited - cube adapter in shop west wall | |
| 08/01/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.4.2 - relocatable power taps shall be directly connected to a permanently installed receptacle - kitchen, outside | |
| 08/01/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.4.3 - relocatable power taps shall not extend through walls - shop west wall | |
| 08/01/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.5 - extension cords shall not be used as a substitute for permanent wiring - shop, outside wleding, battery charging | |
| 08/01/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.5.3 - extension cords shall be without splices, deterioration, or damage - several throughout | |
| 08/01/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.6 - open junction boxes shall be prohibited - junction box in restroom, receptacles outside front door and cooler, receptacle in kitchen | |
| 08/01/2005 | VIOL - BUILDING SVCS & SYSTEMS | Violation | 605.1 - identified electrical hazards shall be abated - remove fan from shower in restroom, install GFI near sink in kitchen |