Case: T05FR01185

Parcel: 13419042D


Addresses:

7220 E BROADWAY BL


Inspection Status: Compliance

Inspection History: INSP - FULL

Case Number - T05FR01185

Inspection Description - INSP - FULL

Inspection Status - Compliance

Date Description Inspector Results Comments
12/15/2005 INSP - FULL Compliance complete final
07/29/2005 INSP - FULL Correction Required TFC-906 The sprinkler system shall be serviced annully and a service tag attaacted.
TFC_906.1 Shall have the fire extinguihers serviced annully.
TFC-1008 Back exit door blocked. you shall clear the exit path.
TFC-315.2 Storage shall be 18" from the sprinkler heads.on the west wall, and the east wall.
Make sure the emergency illumination back up lights get tested every three months.If the light will not go on when testing replace with new battery.
TFC-315.2 In the stock room in back the roofing material has falling on to the sprinkler heads.You shall have this problem corrected.