Inspection History Details
Inspection Status: Approved
Inspection History: INSP - REINSPECTION
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 12/19/2005 | INSP - REINSPECTION | Approved | ok | |
| 10/21/2005 | INSP - REINSPECTION | Violation | On 10-7-05, fire sprinkler reports where due, all corrections had to be made by then, as per previous pre citation letter 9-15-05. There has been no invoice or other proof that corrections have been made. The following sprinkler corrections must be as per fire code requirements. IFC 901.6 1). Kitchen. Lower heads as per report 2). Kitchen. Replace corroded heads by dishwasher. 2). Upgrade system as per hood system report. Please send proof of corrections by 11-18-05. Reports have been enclosed. |
|
| 09/15/2005 | INSP - REINSPECTION | Violation | 1). Fire drill shall be conducted. Date to be determined by August 31, 2005. IFC 404.2 2). Fire sprinkler test and inspection report shall be submitted to TFD ands required repairs shall be completed. IFC 901.6 3). Fire alarm test and inspection report shall be submitted to TFD ands required repairs shall be completed. IFC 901.6 |